-COOLING operation the air channels are parallel through the unit (no heat
-/aftercooling is connected, the icons for these components will be
In the installer menu you can see/change the setpoints for BYPASS
T1/SET Bypass Tmin = Minimum outdoor temperature, where BYPASS
T3/SET Bypass Tmax = Minimum extract air temperature, where BYPASS
The setpoint for supply air temperature (T2) in connection with aftercooling is identical
with the T1/SET bypass Tmin.
-/aftercooling coils are installed they are controlled by the same setpoints and
as the built-in BYPASS-COOLING function. I.e. Pre-/aftercooling and
bypass are always switched on at the same time.
If Aftercooling is installed it will be used together with “cooling recovery mode” if the
outdoor temperature (T1) is higher than the extrac
The setpoint for AUTOMATIC BYPASS-COOLING can be adjusted as follows:
1 Press RIGHT for 10 sec., until the installer menu is active (the ventilation
2 Press RIGHT until the BYPASS-COOLING icon (parallel air channels on the
display) flashes slowly.
NB. The display shows the actual temperatures in all fields.
3 Press CENTER and the actual setpoints for BYPASS-COOLING are shown on
4 Press CENTER and the setpoint for T1/SET bypass Tmin will flash quickly,
together with the icons for pre-/aftercoolers if any is installed.
5 Press UP/DOWN to change the setpoint for T1/ SET bypass Tmin, and con-
6 The setpoint for T3/Bypass Tmax will now flash quickly together with the
icons for pre-/aftercoolers if any is installed.
7 Press UP/DOWN to change the setpoint for T3/ SET bypass Tmax and con-
firm by pressing CENTER. If set point is set to “OF” the BYPASS-COOLING
8 Press RIGHT for 10 sec. until the installer menu closes (the ventilation unit
Unit in bypass-cooling mode