STXC2 User’s guide
Version 2.0
12 of 30
With 48 seconds remaining the control system gives a feedback about the filter test.
If the selected ”filter check value” is near the maximum air volume that the ventilation unit
can handle, the filter test will fail.
If a lower air volume is accepted in the week program, the filter test can be made
another time with a lower ”filter check value”.
But if a lower air volume isn’t accepted in the week program, the ventilation unit can’t
run with automatic filter surveillance.
In the configuration menu the function automatic filter surveillance (menu point ”Auto
filter surv.”) is then going to be disabled. See service engineer’s guide for further
information.
After 400 seconds (approximately 7 minutes) the ventilation unit is ready for use.
Filter configuration
Check at m3h 02500
Accepted d/Pa 0060
Start filtertest ENTER
Technical data
Main menu Monday 12:21
Measuring wait sec. 048
Filter test failed