Page 31 of 39
The device is able to drain some water
but does not reach the expected
performance.
1. Air temperature and / or humidity drops
2.
Humidity Level on the controller require calibration
The device has entered the defrost cycle working
state
Air filter is too dirty or clogged.
Low refrigerant charge, cause by possible leakages
Air leaks, such as
loose caps or leaking at supply /
return air ducting.
The compressor is damaged
The
air duct is not installed properly, and the air
volume is insufficient
After installation, commissioning and
shutdown after a period of time, water
overflows from the mach
ine.
1. The machine is not equipped with proper drainage,
the water cannot be removed
The
drainage is not connected properly, or the piping
is illogical, and the water cannot be drained out
Some of the drainage pipes are at higher level than
the machine drainage hole
Fresh air damper not working
1. Connection to damper not properly connected.
2.
Loose connection in ventilation control circuit
Loose connection in damper power circuit.
4. Defective fresh air damper.