EasyManua.ls Logo

Data Aire DAP III - Control Expansion Module Configuration (Read;Write-Optional); Control Expansion Module Configuration (Read Only-Optional)

Data Aire DAP III
21 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Object Identifier Type Description Units
1.3.6.1.4.1.22731.1.2.2.9.0 INTEGER
Chilled Water Runtime
This applies to chilled water units only
Hours
1.3.6.1.4.1.22731.1.2.2.10.0 INTEGER
Discharge Temperature Sensor Calibration
Optional discharge air temperature sensor required
0.1°F
1.3.6.1.4.1.22731.1.2.2.11.0 INTEGER
Chilled Water Temperature Sensor Calibration
Optional chilled water temperature sensor required
0.1°F
7.6 Control Expansion Module Configuration (Read/Write-Optional)
Note: these points do not apply to Mini-DAP III panel
Object Identifier Type Description Units
1.3.6.1.4.1.22731.1.2.2.12.0 INTEGER (45..61)
Low Discharge Temp Limit
This optional setting requires an
optional discharge air temperature
sensor
°F
1.3.6.1.4.1.22731.1.2.2.13.0 INTEGER (40..60)
Chilled Water Available Limit
Optional chilled water temperature
sensor required. This applies to
energy saver units.
°F
7.7 Control Expansion Module Configuration (Read Only-Optional)
Note: these points do not apply to Mini-DAP III panel
Object Identifier Type Description Units
1.3.6.1.4.1.22731.1.2.2.14.0 DisplayString
(SIZE (0..40))
Custom Alarm Message 4
Optional factory programmed alarm
message.
N/A
1.3.6.1.4.1.22731.1.2.2.15.0 INTEGER (0..900)
Optional Alarm 4 Delay
Seconds
1.3.6.1.4.1.22731.1.2.2.16.0 INTEGER
checkHumidCylinder(1)
customAlarm4(2)
fanMotorOverload(3)
humidLockout(4)
localAlarm(5)
heatAndHumidLockout(6)
heatLockout(7)
standbyPumpOn(8)
upsOn(9)
highCondensateLevel(10)
Optional Alarm 4 Configuration
N/A
1.3.6.1.4.1.22731.1.2.2.17.0 INTEGER
none(1)
one-compressor(2)
two-compressors(3)
Energy Saver Configuration
Factory setting
N/A
1.3.6.1.4.1.22731.1.2.2.18.0 INTEGER
none(1)
chilled-water(2)
energy-saver(3)
aux-chilled-water(4)
Chilled Water Configuration
Factory setting
N/A
1.3.6.1.4.1.22731.1.2.2.19.0 INTEGER
0-10 VDC(1)
Water Valve Configuration
Factory setting
N/A
Document 600-000-615
14

Other manuals for Data Aire DAP III

Related product manuals