1 Overview
The DAP III control panel supports SNMPv1and SNMPv2c protocol interface for a system
monitoring. This document describes all requirements in the DAP III to implement the
SNMPv1/v2c interface; it also provides all the DAP III SNMP objects definition that the DAP III
supports.
Note: Data Aire does not provide the SNMP tools or monitoring applications. The customer is
responsible for these tools or monitoring software.
2 Hardware Requirements and Installation
2.1 Required Network Card
2.1.1 The SNMP protocol interface requires a Data Aire Ethernet network card to be installed
into the DAP III Display board. The Ethernet card part number is 160-400-385. This card is
compliant with IEEE 802.3/802.3u 100BaseTX Ethernet standard and auto-negotiation at
10Mbps/ 100 Mbps.
RJ-45 CONNECTOR BOARD CONNECTOR
Figure 1: Data Aire Ethernet Communications Network card
2.2 Network Card Installation
2.2.1 For SNMP interface, connect an Ethernet Communications network card to the
Communication Header J1 of the DAP III Display board. See figure 2 for the DAP III
Display board with an Ethernet card installed.
After installing the network card, go to menu 6-1 – Unit and Network ID in Group menu 6
to set the unit network ID and to menu 6-2 –Network protocol to configure the network
protocol. Menu 6-2 to 6-7 are locked menus, refer to the DAP III Operation Manual for the
procedure of how to unlock these menus before entering IP address. It is recommended to
reset the DAP III panel after changing the network protocol, IP adress or the unit ID
number.
Document 600-000-615