Network Variable Network Variable Type Description Units
highPressureC1(12)
lowPressureC1(13)
highPressureC2(14)
lowPressureC2(15)
smokeDetect(16)
noWaterFlow(17)
dischargeSensor(18)
chilledWaterSensor(19)
highTemperature(20)
lowTemperature(21)
highHumidity(22)
lowHumidity(23)
fanOverload(24)
localAlarm1(25)
localAlarm2(26)
localAlarm3(27)
localAlarm4(28)
standbyPumpOn(29)
upsOn(30)
customAlarm1(31)
customAlarm2(32)
customAlarm3(33)
customAlarm4(34)
humidInhibited(35)
reheatInhibited(36)
reheatAndHumidInhibited(37)
lowDischargeAlarm(38)
manualOverride(39)
highCondensate(40)
unitInStandbyHeldOff(41)
checkHumidCylinder(42)
7.5 Control Expansion Module Status (Read Only-Optional)
Note: these points do not apply to Mini-DAP III panel
Object Identifier Type Description Units
1.3.6.1.4.1.22731.1.2.2.1.0 INTEGER
not installed(0)
installed(non-zero)
Control Expansion Module Installed
N/A
1.3.6.1.4.1.22731.1.2.2.2.0 INTEGER
Chilled Water Temperature
Optional chilled water sensor required
0.1°F
1.3.6.1.4.1.22731.1.2.2.3.0 INTEGER
Discharge Air Temperature
Optional Discharge Air temperature sensor required
0.1°F
1.3.6.1.4.1.22731.1.2.2.4.0 INTEGER
Chilled Water Valve Open
This applies to Chilled water or Energy saver unit
only.
%
1.3.6.1.4.1.22731.1.2.2.5.0 INTEGER
Chilled Water Utilization Over Last Hour
This applies to Chilled water or Energy saver units.
%
1.3.6.1.4.1.22731.1.2.2.6.0 INTEGER
Heater 2 Runtime
Hours
1.3.6.1.4.1.22731.1.2.2.7.0 INTEGER
Heater 3 Runtime
Hours
1.3.6.1.4.1.22731.1.2.2.8.0 INTEGER
Energy Saver Runtime
This optional point applies to energy saver units
only
Hours
Document 600-000-615