Object Identifier Type Description Units
1.3.6.1.4.1.22731.1.2.1.58.0 INTEGER
off(0)
on(non-zero)
Custom alarm #4
Optional alarm. External alarm input required
Factory programmed custom message required
N/A
1.3.6.1.4.1.22731.1.2.1.59.0 INTEGER
off(0)
on(non-zero)
Humidification inhibited
Optional alarm. External alarm input required.
Humidification is inhibited when alarm goes off.
N/A
1.3.6.1.4.1.22731.1.2.1.60.0 INTEGER
off(0)
on(non-zero)
Reheat inhibited
Optional alarm. External alarm input required.
Reheat is inhibited when alarm goes off.
N/A
1.3.6.1.4.1.22731.1.2.1.61.0 INTEGER
off(0)
on(non-zero)
Reheat and humidification inhibited
Optional alarm. External alarm input required.
Reheat and humidification are inhibited when
alarm goes off.
N/A
1.3.6.1.4.1.22731.1.2.1.62.0 INTEGER
off(0)
on(non-zero)
Low discharge air temperature
Optional alarm. Optional discharge air
temperature sensor required.
N/A
1.3.6.1.4.1.22731.1.2.1.63.0 INTEGER
off(0)
on(non-zero)
Manual override: Check bypass switches
Standard alarm. Manual override switch is on
N/A
1.3.6.1.4.1.22731.1.2.1.64.0 INTEGER
off(0)
on(non-zero)
High condensate water level
Standard alarm on Ceiling unit, optional alarm
on Floor mounts units.
N/A
1.3.6.1.4.1.22731.1.2.1.65.0 INTEGER
off(0)
on(non-zero)
Unit in standby, all functions held off
Optional alarm. Control input signal required
Factory setting required
N/A
1.3.6.1.4.1.22731.1.2.1.117 INTEGER
off(0)
on(non-zero)
Alarm: Chilled water temperature sensor
problem
This alarm requires optional chilled water sensor
N/A
1.3.6.1.4.1.22731.1.2.1.122 INTEGER
off(0)
on(non-zero)
Alarm: Check Humidifier Cylinder
This alarm requires optional humidifier cylinder
alarm contact from humidifier controller
N/A
7.2 Control Module Control (Read/Write)
Network Variable Network Variable Type Description Units
1.3.6.1.4.1.22731.1.2.1.66.0 INTEGER
off(0)
on(non-zero)
Cooling Inhibited
Cooling is inhibited by BMS or
BAS
N/A
1.3.6.1.4.1.22731.1.2.1.67.0 INTEGER
off(0)
on(non-zero)
Heating Inhibited
Heating is inhibited by BMS or
BAS
N/A
1.3.6.1.4.1.22731.1.2.1.68.0 INTEGER
off(0)
on(non-zero)
Humidification Inhibited
Humidifier is inhibited by BMS
or BAS
N/A
1.3.6.1.4.1.22731.1.2.1.69.0 INTEGER
off(0)
on(non-zero)
Dehumidification Inhibited
Dehumidification is inhibited by
BMS or BAS
N/A
1.3.6.1.4.1.22731.1.2.1.70.0 INTEGER
off(0)
on(non-zero)
Fan Inhibited
Fan is inhibited by BMS or BAS
N/A
1.3.6.1.4.1.22731.1.2.1.71.0 INTEGER
Unit on(0)
Standby Mode
Unit on/off control
oint b
N/A