Object Identifier Type Description Units
4-7 VDC(2)
6-9 VDC(3)
7-10 VDC(4)
2-10 VDC(5)
1.3.6.1.4.1.22731.1.2.2.20.0 INTEGER
normal(1)
reverse(2)
Reverse Water Valve Configuration
Factory setting
N/A
7.8 Relay Module Status (Read Only-Optional)
Note: these points do not apply to Mini-DAP III panel
Object Identifier Type Description Units
1.3.6.1.4.1.22731.1.2.3.1.0 INTEGER
not installed(0)
installed(non-zero)
Relay Module Installed
This applies when unit has an optional Relay
module installed
N/A
1.3.6.1.4.1.22731.1.2.3.2.0 INTEGER
Humidifier Valve Open
This applies when unit has an optional
modulating humidifier
%
1.3.6.1.4.1.22731.1.2.3.3.0 INTEGER
Compressor 3 Runtime
This applies when unit has four stages tandem
compressors
Hours
1.3.6.1.4.1.22731.1.2.3.4.0 INTEGER
Compressor 4 Runtime
This applies when unit has four stages tandem
compressors.
Hours
1.3.6.1.4.1.22731.1.2.3.5.0 INTEGER
Condenser Runtime
Hours
7.9 Relay Module Configuration (Read/Write-Optional)
Note: these points do not apply to Mini-DAP III panel
Object Identifier Type Description Units
1.3.6.1.4.1.22731.1.2.3.6.0 INTEGER
none(1)
every6hours(2)
every12hours(3)
every24hours(4)
every36hours(5)
every48hours(6)
every60hours(7)
every72hours(8)
every84hours(9)
every96hours(10)
Autoflush Time
Use on unit with
an optional Infra-
red humidifier
only.
N/A
7.10 Relay Module Configuration (Read Only-Optional)
Note: these points do not apply to Mini-DAP III panel
Object Identifier Type Description Units
1.3.6.1.4.1.22731.1.2.3.7.0 OCTET STRING
Each octet re
p
resents one alarm
Alarm Relay 2 Settings
N/A
Document 600-000-615
15