3 Communication Port Setting
For SNMP communication UDP port setting is 161, refer to the DAP III Operation Manual for the
procedure to enter an IP address and port setting to the DAP III.
4 Community Data string
The Data Aire DAP III SNMP community data string is default to “public”.
See section 7.3 for community string override OID.
5 Sending Traps on Alarms
The DAP III with SNMP interface can be configured to send out traps on alarms to two
different IP addresses. These IP addresses are programmed on menu 6-12 SNMPv2
Manager 1 Address and menu 6-14 SNMPv2 Manager 2 Address of the DAP III using the
front panel keypad. These menus are locked menus; they must be unlocked before any
programming can be done. See DAP III IOM for the procedure of how to unlock these
menus.
The alarms’ selection for traps can be selected using menu 6-13 SNMPv2 Manager 1
Notifications and menu 6-15 SNMPv2 Manager 2 Notifications. When selected alarm
occurs, DAP III will send an alert trap to the assigned Manager IP address that is
programmed in menu 6-12 or 6-14.
6 MIB (Management Information Base) file
The MIB file of the DAP III control panel can be downloaded from Data Aire website at
http://www.dataaire.com
in System Controls- Data Alarm Processor III (DAP III) page or contact
Data Aire technical support.
7 SNMP Object Definitions for DAP III
7.1 Control Module Status (Read Only)
Object Identifier Type Description Units
1.3.6.1.4.1.22731.1.2.1.1.0 INTEGER
off(0)
on(non-zero)
Dehumidifying
Unit is in the dehumidification cooling mode,
unit must have a reheat for this function to be
available
N/A
1.3.6.1.4.1.22731.1.2.1.2.0 INTEGER
off(0)
on(non-zero)
Humidifying
Unit is in the humidification mode, reheat will
be inhibited when humidifier is on
N/A
1.3.6.1.4.1.22731.1.2.1.3.0 INTEGER
off(0)
on(non-zero)
Energy Saver
Optional function. Unit must be an energy saver
model and a chilled water sensor must be
installed.
N/A
1.3.6.1.4.1.22731.1.2.1.4.0 INTEGER
off(0)
Cooling Held
Cooling is in inhibited mode
N/A
Document 600-000-615