Object Identifier Type Description Units
on(non-zero)
1.3.6.1.4.1.22731.1.2.1.5.0 INTEGER
off(0)
on(non-zero)
Heating Held
Heating is in inhibited mode
N/A
1.3.6.1.4.1.22731.1.2.1.6.0 INTEGER
off(0)
on(non-zero)
Humidification Held
Humidification is in inhibited mode
N/A
1.3.6.1.4.1.22731.1.2.1.7.0 INTEGER
off(0)
on(non-zero)
Dehumidification Held
Dehumidification is inhibted
N/A
1.3.6.1.4.1.22731.1.2.1.8.0 INTEGER
off(0)
on(non-zero)
Reheating During Dehumidification
Heating is on during dehumidification mode
N/A
1.3.6.1.4.1.22731.1.2.1.9.0 INTEGER
Return Temperature
This represents the current return air
temperature
0.1°F
1.3.6.1.4.1.22731.1.2.1.10.0 INTEGER
Current Humidity
This represents the current relative humidity
0.1%RH
1.3.6.1.4.1.22731.1.2.1.11.0 INTEGER (0..5)
Cooling Stages On
Cooling stages are currently on – This point
applies to DX unit only
N/A
1.3.6.1.4.1.22731.1.2.1.12.0 INTEGER (0..4)
Heating Stages On
Heating stages are currently on
N/A
1.3.6.1.4.1.22731.1.2.1.13.0 INTEGER
High Temperature Over Last 24 Hours
Maximum return air temperature in the last 24
hours of operation
0.1°F
1.3.6.1.4.1.22731.1.2.1.14.0 INTEGER
Low Temperature Over Last 24 Hours
Minimum return air temperature in the last 24
hours of operation
0.1°F
1.3.6.1.4.1.22731.1.2.1.15.0 INTEGER
High Humidity Over Last 24 Hours
Maximum return air humidity in the last 24
hours of operation
0.1°F
1.3.6.1.4.1.22731.1.2.1.16.0 INTEGER
Low Humidity Over Last 24 Hours
Minimum return air humidity in the last 24
hours of operation
0.1°F
1.3.6.1.4.1.22731.1.2.1.17.0 INTEGER
Cooling Utilization Over Last Hour
Percentage of cooling is used in the last hour of
operation; this point applies to DX unit.
%
1.3.6.1.4.1.22731.1.2.1.18.0 INTEGER
Heating Utilization Over Last Hour
Percentage of heating is used in the last hour of
operation
%
1.3.6.1.4.1.22731.1.2.1.19.0 INTEGER
Humidifier Utilization Over Last Hour
Percentage of humidifier is used in the last hour
of operation
%
1.3.6.1.4.1.22731.1.2.1.20.0 INTEGER
Compressor 1 Runtime
This point applies to DX unit with one
compressor
Hours
1.3.6.1.4.1.22731.1.2.1.21.0 INTEGER
Compressor 2 Runtime
This point applies to DX unit with dual
compressor
Hours
1.3.6.1.4.1.22731.1.2.1.22.0 INTEGER
Heater 1 Runtime
Hours
1.3.6.1.4.1.22731.1.2.1.23.0 INTEGER
Humidifier Runtime
Hours
Document 600-000-615
6