Object Identifier Type Description Units
1.3.6.1.4.1.22731.1.2.1.24.0 INTEGER
Blower Runtime
Hours
1.3.6.1.4.1.22731.1.2.1.25.0 INTEGER
Dehumidifier Runtime
Hours
1.3.6.1.4.1.22731.1.2.1.26.0 INTEGER
off(0)
on(non-zero)
Water detected under floor: Check probe
Standard alarm on Data Aire series units
N/A
1.3.6.1.4.1.22731.1.2.1.27.0 INTEGER
off(0)
on(non-zero)
No air flow: Check belt and motor
Standard alarm
N/A
1.3.6.1.4.1.22731.1.2.1.28.0 INTEGER
off(0)
on(non-zero)
Dirty filter: Check filters
Standard alarm on Data Aire series, optional on
ceiling units
N/A
1.3.6.1.4.1.22731.1.2.1.29.0 INTEGER
off(0)
on(non-zero)
Humidifier problem: Check water pressure
Standard alarm on Data Aire series, optional on
ceiling units
N/A
1.3.6.1.4.1.22731.1.2.1.30.0 INTEGER
off(0)
on(non-zero)
Low voltage warning: Check unit
Standard alarm on unit with DAP III
N/A
1.3.6.1.4.1.22731.1.2.1.31.0 INTEGER
off(0)
on(non-zero)
Fire stat alarm: Unit shutdown
Standard alarm, unit will temporary shutdown
when this alarm goes off
N/A
1.3.6.1.4.1.22731.1.2.1.32.0 INTEGER
off(0)
on(non-zero)
Compressor short cycle warning
Standard alarm on DX units. This does not apply
to chilled water units. Compressor starts and
stops10 times in one-hour period.
N/A
1.3.6.1.4.1.22731.1.2.1.33.0 INTEGER
off(0)
on(non-zero)
Power problem or unit restart
Standard programmable alarm. Power loses then
restores
N/A
1.3.6.1.4.1.22731.1.2.1.34.0 INTEGER
off(0)
on(non-zero)
Humidity sensor problem
Standard alarm. Humidity sensor reading is out
of range
N/A
1.3.6.1.4.1.22731.1.2.1.35.0 INTEGER
off(0)
on(non-zero)
Temperature sensor problem
Standard alarm. Temperature reading is out of
range
N/A
1.3.6.1.4.1.22731.1.2.1.36.0 INTEGER
off(0)
on(non-zero)
Scheduled maintenance due
Standard programmable alarm.
N/A
1.3.6.1.4.1.22731.1.2.1.37.0 INTEGER
off(0)
on(non-zero)
High pressure/Internal overload: Comp 1
Standard alarm on DX unit with one
compressor. Compressor’s high pressure switch
is open
N/A
1.3.6.1.4.1.22731.1.2.1.38.0 INTEGER
off(0)
on(non-zero)
Low pressure C1: Automatic reset
Standard alarm on DX unit with one
compressor. Compressor’s low pressure switch
is open
N/A
1.3.6.1.4.1.22731.1.2.1.39.0 INTEGER
off(0)
on(non-zero)
High pressure/Internal overload: Comp 2
Standard alarm on DX unit with dual
compressor. Compressor’s high pressure switch
is open
N/A
1.3.6.1.4.1.22731.1.2.1.40.0 INTEGER
off(0)
on(non-zero)
Low pressure C2: Automatic reset
Standard alarm on DX unit with dual
compressor. Compressor’s low pressure switch
is open
N/A