12
2.1.6 Field Piping, Remote Condenser/Condensing Unit Below Evaporator
2.2 Water/Glycol Cooled Unit Piping
Therequiredeldinstalleduidcoolerpipesizesmayormaynotbethesameastheconnection
sizesontheuidcooler(referto2.2.2and2.2.3forconnectionsizing).Thiswilldependonthe
length of pipe and the calculated pressure drop of peripheral components.
Water cooled units may also be connected to building water or tower water sources. Pipe size will
dependonlengthofrunandthemaximumwaterowrequired.
Shut-offvalves(eldprovided)shouldbeinstalledwithinafewfeetoftheinletandoutletconnec-
tionsoftheevaporatortoallowtheunittobeisolatedforservice.Drain/llvalvesshouldbelocated
at the lowest point on the connected piping.
Allwater/glycolcooledunitsareshippedwithplate/nheatexchangersasstandardequipment.A
strainerisshippedlooseandistobeeldinstalledinthesupplylinewithshut-offvalves(eldpro-
vided) before and after the strainer. The strainers and water/glycol piping must be cleaned on a
periodic basis. If the unit is shipped with shell and tube condensers strainers are not required not
shipped with the unit.
All water pipes have a cap installed on the end of the pipe for pressure testing the system. These
caps need to be removed before installing the piping to the units. Use a tube cutter for smaller pipes
and a reciprocating saw with a metal cutting blade for larger pipe sizes or if there is a clearance
problem. All connections need to be cleaned before connections are brazed together.