8.0 REGULAR MAINTENANCE ITEMS
8.1 Air Filters
Airltersshouldbecheckedonaregularbasisandchangedwhentheybecomedirty.Thiswillen-
sureefcientoperationoftheunit.Althoughtheunithasadirtylteralarm,thisshouldnotberelied
onastheonlydeterminantforreplacinglters.Amaladjustedlterdifferentialpressureswitchmay
notgiveaproperindicationofacloggedlter.
To check the pressure differential switch for proper adjustment, temporarily cover about 75% of the
return air opening using heavy cardboard or similar material. The alarm should energize when 75%
oftheairisblocked,simulatingdirtylters.Ifthealarmenergizesprematurelyordoesnotenergize
at all, the pressure switch should be adjusted. Doors must remain closed when determining if an
adjustment is necessary.
Spareltersshouldbekeptonstockasthesetendtobeafrequentlyreplacedmaintenanceitem.
Filters require changing as often as monthly. Note also that construction dust on new installations
willquicklyclognewlters.
WARNING:Airltersthatrequirechangingcanrestrictairowandcreateproblemssuch
as poor air distribution.
8.2 Humidier Canisters
SteamgeneratortypehumidierisstandardongForceGTseriesofequipment.Thereisnomain-
tenance required other than to replace the canister as required. This frequency will depend on
usageandwatertype.Asetofmanufacturersinstructionsforthehumidierissentaspartofthe
paperwork placed inside the unit when it ships.
8.3 Fuses
Fuses may occasionally require changing especially with installations where the voltage is not con-
sistent. Drops in voltage can create brief periods of high amps draw, causing fuses to blow. Always
replace fuses with those of the equivalent rating with regard to: 1) amperage, 2) voltage, and 3)
speed. For instance motors are inductive loads which require time delay fuses. Electric reheat and
humidiersareresistiveloadsrequiringfastactingfuses.
8.4 Heating Elements
Heating elements do not normally require maintenance. However, sometimes they accumulate a
lmordirtwhenunusedforextendedperiodsoftime.Whenenergized,theburningdebriscancre-
ate smoke or an unpleasant odor. To help prevent this, periodic cleaning is recommended.
8.5 Refrigerant Filter Drier
Factoryinstalledrefrigerantlterdriersdonotrequiremaintenanceorreplacementunlessthesys-
tem has been opened. When replacing compressors or other repairs that open the refrigeration
systemtotheatmosphere,itisalwaysadvisabletoreplacethelterdrier.Theequivalenttypeand
size should be used.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Data Aire gForce GT series and is the answer not in the manual?

Data Aire gForce GT series Specifications

General IconGeneral
BrandData Aire
ModelgForce GT series
CategoryAir Conditioner
LanguageEnglish

Related product manuals