1.0 INSTALLATION
ThereisnointentonthepartofDataAire,Inc.todenelocalcodesorstatuteswhich
may supersede common trade practices. The manufacturer assumes no responsibility for
their interpretation. Consult local building codes and National Electrical Code (NEC) for
special installation requirements.
1.1 Room Considerations
Precision air conditioning equipment is designed to control spaces within close tolerances of tem-
peratureandhumidity.However,theroommustbebuiltwithapropervaporbarrier.Almofpoly-
ethyleneisoftenusedonwallsandceilings.Wallsandoorsmustalsobepaintedwithvapor-seal
paint. Failure to provide a vapor barrier can compromise space conditions.
Introduction of outside air into the space should be minimized. Outside air in excess of 5% of the
totalcirculatedairvolumecanhaveasignicanteffectontheoverallspaceconditionsandresultin
poor space control.
1.2 Inspection
This Data Aire unit has been factory run-tested and has gone through a comprehensive inspec-
tion prior to its packaging and shipment to ensure that it arrives in excellent condition. However,
shipping damage can occur and a visual inspection of the outer crating immediately upon delivery
should be performed.
Note any external damage or transportation damage on the freight carrier’s forms. Inspect the unit
itselfforinternaldamage.Aclaimshouldbeledwiththeshippingcompanyiftheequipmentis
damaged or incomplete.
Looseitemssuchasremotecontrolpanels,disconnectswitchhandles,sparebeltsandsparelters
are packed inside the unit. Refer to the yellow shipping tag located on the unit door for details.
Freight damage claims are the responsibility of the purchaser. Action to recover losses
shouldbeledimmediately.Pleasenotifyfactorypersonnelofanyclaims.
1.3 Rigging
Move the unit in its upright position to the installation site. It is recommended that the unit be pro-
tected from damage to the decorative doors during any storage or moving. Removal of the decora-
tive doors is easily accomplished and may be done without moving the equipment.
The shipping skid should be left in place if the unit is being moved with a forklift. If the unit is being
lifted, use spreader bars to prevent damage to the doors and panels.
The unit has 3/4” holes in the shipping skid to which casters with 3/4” stems can be attached. This
allows easy movement down halls, into elevators and through doorways. If clearance is a problem
the casters may be inserted directly into the bottom of the 1” tubular steel corner posts at the bottom
of the unit.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Data Aire gForce GT series and is the answer not in the manual?

Data Aire gForce GT series Specifications

General IconGeneral
BrandData Aire
ModelgForce GT series
CategoryAir Conditioner
LanguageEnglish

Related product manuals