2.7.7 Field Piping, Remote Condenser Below Evaporator
2.7.8 Water/Glycol Cooled Unit Piping
Water/Glycol-cooled units are factory-charged and tested. Field-supplied and eld-installed piping is
required from the unit to building water or tower water sources or the uid cooler (i.e., dry cooler) and
pump package. Pipe size will depend on length of run and the maximum water ow required.
The required eld installed uid cooler pipe sizes may or may not be the same as the connection sizes
on the uid cooler (refer to the Fluid Cooler User Manual for connection sizing). This will depend on the
length of pipe and the calculated pressure drop of peripheral components.
Shuto󰀨 valves (eld provided) should be installed within a few feet of the inlet and outlet connections
of the evaporator to allow the unit to be isolated for service. Drain/ll valves (eld provided) should be
located at the lowest point on the connected piping.
Water/glycol cooled units are shipped with plate/n heat exchangers as standard equipment. A strainer
(Data Aire provided) is shipped loose and is to be eld installed in the supply line with shut-o󰀨 valves
(eld provided) before and after the strainer. The strainers and water/glycol piping must be cleaned
on a periodic basis. If the unit is shipped with optional shell and tube condensers, strainers are not
required and not shipped with the unit.
All water pipes have a cap installed on the end of the pipe prior to shipment from the factory for pres-
sure testing the system. These caps need to be removed before installing the piping to the units. Use
a tube cutter for smaller pipes and a reciprocating saw with a metal cutting blade for larger pipe sizes
or if there is a clearance problem. All connections need to be cleaned before connections are brazed
together.