20
2.7.10 Connection Sizes, Water/Glycol Cooled Units
Evaporator Model Water In Connection Water Out Connection
GUWX-022XX
GUGX-022XX
1-1/8” (29mm) O.D. 1-1/8” (29mm) O.D.
GUWX-036XX
GUGX-036XX
1-5/8” (41mm) O.D. 1-5/8” (41mm) O.D.
GUWX-045XX
GUGX-045XX
1-5/8” (41mm) O.D. 1-5/8” (41mm) O.D.
GUWX-070XX
GUGX-070XX
1-5/8” (41mm) O.D. 1-5/8” (41mm) O.D.
GUWX-091XX
GUGX-091XX
2-1/8” (54mm) O.D. 2-1/8” (54mm) O.D.
GUWX-125XX
GUGX-125XX
2-1/8” (54mm) O.D. 2-1/8” (54mm) O.D.
* D=Downow U=Upow
2.7.11 Connection Sizes, Fluid Coolers (Dry Coolers)
Evaporator
Model
Fluid Cooler Model
Water In
Connection
Water Out
Connection
GUWX-022XX
GUGX-022XX
GHFC-053 2-1/8” 2-1/8”
GHFC-074 2-1/8” 2-1/8”
GHFC-130 2-5/8” 2-5/8”
GUWX-036XX
GUGX-036XX
GHFC-060 2-1/8” 2-1/8”
GHFC-074 2-1/8” 2-1/8”
GHFC-141 2-5/8” 2-5/8”
GUWX-045XX
GUGX-045XX
GHFC-074 2-1/8” 2-1/8”
GHFC-106 2-5/8” 2-5/8”
GHFC-176 2-5/8” 2-5/8”
GUWX-070XX
GUGX-070XX
GHFC-084 2-1/8” 2-1/8”
GHFC-106 2-5/8” 2-5/8”
GHFC-176 2-5/8” 2-5/8”
GUWX-091XX
GUGX-091XX
GHFC-141 2-5/8” 2-5/8”
GHFC-176 2-5/8” 2-5/8”
GHFC-310 2-5/8” 2-5/8”
GUWX-125XX
GUGX-125XX
GHFC-176 2-5/8” 2-5/8”
GHFC-215 2-5/8” 2-5/8”
GHFC-352 2-5/8” 2-5/8”