EasyManua.ls Logo

Data Aire gForce Ultra - Liquid Line Solenoid Valve

Default Icon
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
51
5.10.5 Liquid Line Solenoid Valve
Liquid line solenoid valve(s) (LLVS) are a standard feature on this unit. The LLSV are direct acting, NC
(normally closed; i.e. closed when de-energized) solenoid operated valve(s). This has the advantage
that the valve is closed when the system is not running and when the solenoid valve is not energized.
For this reason, an electrical power failure does not lead to any problems with the refrigeration system.
The primary purpose of a solenoid valve in a refrigerant liquid line is to helps prevent refrigerant migra-
tion (i.e., ow into the evaporator) during the OFF cycle.
NOTE: Charging to a full liquid line sight glass should never be the sole
means of determining the correct refrigerant charge. Other parameters such
as superheat, suction pressure, head pressure, sub-cooling and ambient
temperature are also important. A system charged to a clear sight glass is
often overcharged.