Data Aire gForce Ultra - Flooded System Charging; Constant Speed Compressor

Default Icon
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
38
60 37 18
70 43 21
80 49 25
90 55 28
100 61 31
110 67 34
120 74 37
130 80 40
140 86 43
150 92 46
160 98 49
170 104 52
180 110 55
190 117 58
200 123 61
210 129 64
220 135 67
230 141 71
240 147 74
250 153 77
When charging is complete, close the valve on the refrigerant manifold set and close the service
valve on the refrigerant tank. Then go back into menu “H. Calibrate Sensors” and set either the
“Return Air Temp Sensor” or “Discharge Air Temp Sensor” menu oset values back to 0. If a cali-
bration oset value has been determined in the eld that is dierent from 0 bring the oset num-
ber back to this value.
5.5 Flooded System Charging
WARNING: The constant speed compressor must be charged before charg-
ing the variable speed compressor in a dual circuit system.
Flooded systems are supplied with optional liquid receiver and head pressure control valve. When
the ambient temperature falls during cold weather, the head pressure control valve will regulate the
ow of refrigerant to ensure minimum receiver pressure. The condenser is partially ooded with liquid
refrigerant in cold weather. In warm weather the extra refrigerant is stored in the receiver. Therefore,
ooded systems require more refrigerant than fan speed control systems.
5.5.1 Constant Speed Compressor
See the tables for the appropriate charging
1. After the system has been properly evacuated. Calculate the proper charge by following
the steps of the tables below.