Measure the superheat at the compressor suction line at least 6 inches (152 mm) away from the com-
pressor. Compare suction pressure and temperature reading between the dap4 and the manifolds. If
the di󰀨erence between the manifold reading and dap4 reading is more than 5%, check for the EEV wir-
ing and any possible alarms on dap4, or EEV driver. Measure sub-cooling at the liquid line.
When charging is complete, add the correct amount of oil, if the line run exceeds longer than 20m or
66ft. This procedure must be conducted with the system running at high load (compressor at full speed).
ALWAYS use original Danfoss POE oil 160SZ from new cans.
Oil addition is calculated based on refrigerant charge, shown in the table below:
Additional Oil Required (oz)
Note: Additional oil is only needed if pipe run is longer than 20m or 66ft.
Total Refrigerant Weight
(lbs.)
Danfoss Variable Speed
Compressor
Danfoss Fixed Speed
Compressor
20 12 6
30 18 9
40 25 12
50 31 15
60 37 18
70 43 21
80 49 25
90 55 28
100 61 31
110 67 34
120 74 37
130 80 40
140 86 43
150 92 46
160 98 49
170 104 52
180 110 55
190 117 58
200 123 61
210 129 64
220 135 67
230 141 71
240 147 74
250 153 77