EasyManua.ls Logo

Data Aire gForce Ultra - Page 35

Default Icon
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
35
1. After the system has been properly evacuated. Calculate the proper charge by
following the steps of the tables below.
Add the amount of refrigerant needed for the evaporator & condenser + the line-set
then multiply by .80.
Step 1: Select the model and refrigerant charge for evaporator and condenser.
Weight of Refrigerant in Evap + Condenser
Model Starting Charge (lbs.)
GUAX-022XX NA
GUAX-036XX
NA
GUAX-045XX
NA
GUAX-070XX
25
GUAX-091XX
32.5
GUAX-125XX
37.5
Step 2: Since the majority of refrigerant weight is in liquid form in the liquid line, refrigerant
in the hot gas line and suction line is ignored in the charging calculation.
Calculate the total of the liquid line run, then multiply the equivalent feet of line based on
line size by the correct multiplier to get the refrigerant weight needed for the Line-set.
1. Weight of Refrigerant in Liquid Line (lbs. /ft.)
Liquid Line OD (inches) Multiplier
1/2” .067
5/8”
.107
3/4”
.160
7/8”
.223
1-1/8”
.380
Example: If the liquid line of an R-410A system is 150ft of 1-1/8” pipe, then multiply 150 *
0.38 = 57lbs
Step 3: Add refrigerant weights from step 1 and 2 together and multiply by .80 to get the
starting charge.
Example: model GUAX-125XX (37.5 + 57 lbs.) *.80 = 75.6 lbs.
2. Next connect the refrigerant tank to the refrigerant manifold gauge set and make sure the
manifold gauge set is properly purged
3. Then from a vacuum, slowly open the high side liquid line valve on the refrigerant manifold
gauge to feed liquid refrigerant through the high side.
4. Add the amount of refrigerant weight per tables, slowly open the high side liquid line valve
on the refrigerant manifold gauge to feed liquid refrigerant through the high side.

Table of Contents

Other manuals for Data Aire gForce Ultra

Related product manuals