10 ● gForce Ultra User Manual 10-2014
2. INSTALLATION
NOTE:
There is no intent on the part of Data Aire, Inc. to define local
codes or statutes which may supersede common trade practices. The
manufacturer assumes no responsibility for their interpretation. Consult
local building codes and National Electrical Code (NEC) for special
installation requirements.
2.1 Installation Checklist
As a precaution, review the following checklist to ensure proper operation:
Check for any damage
Check all wiring connections
Filters are properly positioned in air intake
WARNING:
Before removing from the packaging inspect the unit for any
damage. Report any damage to the carrier and file a damage claim.
2.2 Room Considerations
Precision air conditioning equipment is designed to control spaces within close
tolerances of temperature and humidity. However, the room must be built with a
proper vapor barrier. A film of polyethylene is often used on walls and ceilings. Walls
and floors must also be painted with vapor-seal paint. Failure to provide a vapor barrier
can compromise space conditions.
Introduction of outside air into the space should be minimized. Outside air in excess of
5% of the total circulated air volume can have a significant effect on the overall space
conditions and result in poor space control.
Install the units as close as possible to the largest heat load.