10-2014 gForce User Manual ● 53
8. CONTROLS
8.1 dap4 Microprocessor Control Panel
The standard controller on all gForce Ultra units is the dap4 microprocessor control
panel. The unit is shipped with factory default settings. The settings can be changed
to meet the controlled space criteria. The dap4™ consists of two main components:
the control module and the display panel. The control module is located in the unit’s
electrical panel. The display panel is mounted on the front door. The two are
connected by special telephone type cable harness
1
. All data displayed on the display
screen originates from the control module. The display panel has a backlit LCD (liquid
crystal display).
Note:
The dap4 microprocessor control panel has an entire manual
dedicated to its use and operation. This manual must be referenced to
complete a thorough unit installation. Start-up is not complete until the
dap4 control panel settings are established.
8.1.1 Control Module
8.1.2
1
Regular telephone cable will not operate. Factory supplied cable is required.

Table of Contents