10-2014 gForce User Manual ● 125
11. RECOMMENDED LINE SIZING
11.1 Hot Gas Lines Single Circuit Units (Up To 200 Equivalent Feet (61 m))
kW
(Tonnage)
50 Feet
(15.2 m)
100 Feet
(30.5 m)
150 Feet
(45.7 m)
200 Feet
(61.0 m)
36 (10.2)
1-1/8 (29)
1-1/8 (29)
1-3/8 (35)
1-3/8 (35)
45 (12.2)
1-1/8 (29)
1-1/8 (29)
1-3/8 (35)
1-3/8 (35)
11.2 Hot Gas Lines Dual Circuit Units (Up To 200 Equivalent Feet (61 m))
kW
(Tonnage)
50 Feet
(15.2 m)
100 Feet
(30.5 m)
150 Feet
(45.7 m)
200 Feet
(61.0 m)
56 (15.6)
1-1/8 (29)
1-1/8 (295)
1-3/8 (35)
1-3/8 (35)
070 (20)
1-1/8 (29)
1-1/8 (295)
1-3/8 (35)
1-3/8 (35)
106 (30)
1-3/8 (35)
1-3/8 (35)
1-3/8 (35)
1-5/8 (41)
11.3 Liquid Lines Single Circuit Units (Up to 200 Equivalent Feet (61 m))
kW
(Tonnage)
50 Feet
(15.2 m)
100 Feet
(30.5 m)
150 Feet
(45.7 m)
200 Feet
(61.0 m)
36 (10.2)
5/8 (16)
7/8 (22)
7/8 (22)
7/8 (22)
45 (12.2)
7/8 (22)
7/8 (22)
7/8 (22)
7/8 (22)
11.4 Liquid Lines Dual Circuit Units (Up to 200 Equivalent Feet (61 m))
kW
(Tonnage)
50 Feet
(15.2 m)
100 Feet
(30.5 m)
150 Feet
(45.7 m)
200 Feet
(61.0 m)
56 (15.6)
5/8 (16)
7/8 (22)
7/8 (22)
7/8 (22)
070 (20)
5/8 (16)
7/8 (22)
7/8 (22)
7/8 (22)
106 (30)
7/8 (22)
7/8 (22)
7/8 (22)
7/8 (22)