28 ● gForce Ultra User Manual 10-2014
The remote shutdown contacts are always terminals # 1 and # 2 on the terminal block
designated TB1. The unit will ship with factory wired metal jumper clip that connects
terminal # 1 to terminal # 2. Remove the clip prior to installing the field wires.
3.7 Remote Alarm Contacts
The dap4 microprocessor control panel provides four (4) remote alarm output
contacts that can be field accessed. The contacts include a Normally Open (NO) or
Normally Closed (NC) on Alarm, dry contact, intended to be used in a control circuit not
exceeding 5 amps at 24 VAC. Use field-supplied Class 1 wiring.
These programmable output contacts will close on a failure and remain closed until the
alarm is no longer present. The terminal designations for these alarm output contact
pairs are:
Remote Alarm Contacts Terminals
TB1
Function
# 11
Remote Alarm 1 (Common)
# 12
Remote Alarm 1 (Normally Closed)
# 13
Remote Alarm 1 (Normally Open)
# 40
Remote Alarm 2 (Common)
# 41
Remote Alarm 2 (Normally Closed)
# 42
Remote Alarm 2 (Normally Open)
# 43
Remote Alarm 3 (Common)
# 44
Remote Alarm 3 (Normally Closed)
# 45
Remote Alarm 3 (Normally Open)
# 48
Remote Alarm 4 (Common)
# 49
Remote Alarm 4 (Normally Closed)
# 50
Remote Alarm 4 (Normally Open)
3.8 Condensate Pumps
A condensate pump is optional. Factory mounted pumps are pre-wired. While no
outside power source is required, field piping is still a requirement.