28 ● gForce Ultra User Manual 10-2014
The remote shutdown contacts are always terminals # 1 and # 2 on the terminal block
designated TB1. The unit will ship with factory wired metal jumper clip that connects
terminal # 1 to terminal # 2. Remove the clip prior to installing the field wires.
3.7 Remote Alarm Contacts
The dap4™ microprocessor control panel provides four (4) remote alarm output
contacts that can be field accessed. The contacts include a Normally Open (NO) or
Normally Closed (NC) on Alarm, dry contact, intended to be used in a control circuit not
exceeding 5 amps at 24 VAC. Use field-supplied Class 1 wiring.
These programmable output contacts will close on a failure and remain closed until the
alarm is no longer present. The terminal designations for these alarm output contact
pairs are:
Remote Alarm Contacts Terminals
Remote Alarm 1 (Normally Closed)
Remote Alarm 1 (Normally Open)
Remote Alarm 2 (Normally Closed)
Remote Alarm 2 (Normally Open)
Remote Alarm 3 (Normally Closed)
Remote Alarm 3 (Normally Open)
Remote Alarm 4 (Normally Closed)
Remote Alarm 4 (Normally Open)
3.8 Condensate Pumps
A condensate pump is optional. Factory mounted pumps are pre-wired. While no
outside power source is required, field piping is still a requirement.