78 ● gForce Ultra User Manual 10-2014
Modulate Min: This is the minimum speed the fan can run at. It is calculated as the
percentage of the Modulate Max. For example, if the Modulate Max is 90% and
Modulate min is 70%, the minimum fan speed is 90%x70% = 63%
Modulate Max: The maximum fan speed allowed
Move the cursor to the title block by pressing the ENTER key stepping through all the
inputs. To return to the main Menu press the ESC key or to view the following screen
press the DOWN key.
The Fan Rack Settings screen will be displayed (values are for reference only):
Ramp step rate: The rate at which the fan will change its speed in any modulation
mode. The default rate is 0.5% per second and ranges from 0.1% per second to 5%