23 • Mini dap4 User Manual
3.9 MENU I – MANUAL CONTROL
MENU I allows manually running different unit components (the Service Level password is required for entry)
In the Main Menu screen press the UP or DOWN key until “I - Manual Control” appears and is highlighted. Press the
ENTER key.
Move the cursor to the title block by pressing the ENTER key. To return to the Main Menu press the ESC key or to
view the following screen press the DOWN key.
The following will be displayed (values are for reference only):
Note: The “Return to Auto:” is programmable from 10 to 300 seconds. Once the time has elapsed the func-
tions will return to normal programmed operation.
Move the cursor to the title block by pressing the ENTER key. To return to the Main Menu press the ESC key or to
view the following screen press the DOWN key.
The following will be displayed (values are for reference only):
Move the cursor to the title block by pressing the ENTER key. To return to the Main Menu or press the ESC key.
Manual Output Mgnt. 1
Return to Auto: 60s
Blower Auto On
Compressor 1 Auto Off
Compressor 2 Auto Off
Reheater Auto Off
Humidifier Auto Off
Manual Output Mgmt. 2
Alarm Auto Off
Cond Aux Rly Auto Off