25 • Mini dap4 User Manual
The following will be displayed (values are for reference only):
Available Selections:
None, One or 1-Elect
1-Elect is the default setting and only allows the reheat to work during dehumidication mode. If One is selected then
reheat allows to work whenever space temperature is below setpoint minus deadband regardless dehumidication
operation.
Once a selection or selections have been made, move the cursor to the title block by pressing the ENTER key
▼ Press the DOWN key to view the next screen:
The following will be displayed (values are for reference only):
Available Selections:
Wtr Vlv (Water Valve): Chill Wtr Cool
Engy Svg Cool
Aux Chill Wtr
Chill Wtr Reg
None
The screen information will vary with each water valve selection. The screen displays for each choice follows (values
are for reference only):
Chill Wtr Cool
Reheat Settings
Reheat Stages: 1 Elect
Water valve Setting
Wtr Vlv: None
Water Valve Settings
Wtr Vlv: Chill Wtr Cool
Wtr Vlv Voltage: 2-10*
Wtr Vlv Action: Direct*
Engy Lockout Time: 15m*