37 • Mini dap4 User Manual
The following will be displayed (values are for reference only):
Move the cursor by pressing the ENTER key. Move the cursor to change the setting.
The following can be changed by pressing the DOWN key:
Channel – Open or Closed
Delay – the range is 0 – 999 seconds
Status – Open or Closed
Once a selection or selections have been made, move the cursor to the title block by pressing the ENTER key
▼ Press the DOWN key to view the next screen.
The following will be displayed (values are for reference only):
Move the cursor by pressing the ENTER key. Move the cursor to change the setting.
The following can be changed by pressing the DOWN key:
Enable – ON or OFF
Note: If (Enable) OFF is selected the Normal, Minimum, Maximum, Offset and Value will not be displayed.
With Enable ON, Normal, Minimum, Maximum, Offset and Value will be displayed and values changed.
Once a selection or selections have been made, move the cursor to the title block by pressing the ENTER key
▼ Press the DOWN key to view the next screen.
The following will be displayed (values are for reference only):
Digital Input
HI CONDENSATE SW
Channel B6
Action: Closed
Delay: 5s
Status: Closed
Analog Input
Humidity Sensor
Enable: ON Channel: B2
Normal 4-20 mA
Minimum: 0.0
Maximum: 100.0
Offset: 0.0
Value: 35.6
Analog Input
Return Air Temp Sensor
Enable: ON Channel: B1
High Res. NTC
Offset: 0.0
Value: 74.1