▼ Press the DOWN key. The following message will be displayed:
▼ Press the ENTER key. The following message will be displayed:
The above screen can be interpreted as: @ 5:28:11 AM on 9/17/11 the temperature was above the high temperature
alarm setpoint. At the time of the alarm the humidity was 54% RH and the temperature was 75.2°F.
Press the ENTER key to move the cursor to - > Scroll Up/Down. Pressing the UP or DOWN key will display alarms
with time, date, relative humidity temperature at time of alarm.
Once all alarms have been viewed, Press the ENTER key to move the cursor to the title block (time and date). Press
the ESC key to return to the Main Menus or Press the DOWN key to see Run Hours.
Component run times may be seen and/or reset through this and consecutive screens.
ALARMS
3 Press Enter
to DATA LOGGER
5:28:11 9/17/11
g Scroll Up/Down?
Ret Air Hi Temp
Humidity: 54%
Return Air: 75.2
o
F
Chilled Water: 0.0
o
F
Run Hours 1 Reset
Blower: 0000 No
Comp 1: 0000 No
Comp 2: 0000 No
Reheat: 0000 No
Humidify: 0000 No
Dehum: 0000 No
Run Hours 2 Reset
Engy Svr: 0000 No
CW Cool: 0000 No
Cond Aux: 0000 No
Reset All Runtimes: No