46 • Mini dap4 User Manual
3. Reheat will be overridden by humidication when the humidier setting is programmed for Computer, Non-Modulat
ing or Computer, Modulating (See Menu J – Factory Settings).
HUMIDIFICATION
1. Humidication will inhibit the reheat if programmed (See Menu J - Factory Settings) for Humidier: Computer Non-
Modulating or Humidier: Computer Modulating. Reheat is allowed during humidication if programmed for
Humidier Comfort, Non-Modulating or Humidier Comfort, Modulating.
2. There is a one (1) minute delay between the stop-to-start of humidication.
3. There is a ve (5) minute delay between the dehumidication and start of humidication.
4. The humidication staging sequence of each adjustment period for ON/OFF of non-modulating humidiers is as
follows:
Humidier is ON at Humidity Setpoint – Humidity Deadband
Humidier is OFF at Humidity Setpoint – 1.0%
5. The humidication staging sequence for a modulating humidier is as follows:
Valve is OPENED at Humidity Setpoint – 1.0%
Valve is CLOSED at Humidity Setpoint – 0.5%
6. When the humidier valve is opened, its position will follow a linear ramp that goes from 25% open with the
humidity at setpoint minus 0.5% to 100% open at setpoint minus humidity deadband.
DEHUMIDIFICATION
1. Dehumidication Mode can be programmed with one or two compressors (dual compressor units only) for
dehumidication and with or without reheat limits (See Menu J – Factory Settings).
2. If dehumidication is programmed for “In Limits” dehumidication will inhibit if the return air temperature drops to
temperature setpoint minus temperature deadband minus 2°F. Dehumidication will be inhibited until the return air
temperature rises to the temperature setpoint. Compressor short-cycle time will not be violated.
3. If dehumidication is programmed for “No Limits” it will remain ON until the humidity setpoint is reached. In this
mode dehumidication has priority and overcooling is disregarded. The reheat sequence will remain the same.
4. If dehumidication is programmed for two (2) compressors, with or without reheat limits, only one (1) compressor
will be allowed if reheat is required.
5. There is a one (1) minute delay between stop-to-start of dehumidication. Compressor short-cycle time delay will
not be violated.
6. There is a ve (5) minute delay between dehumidication and humidication.
7. The compressor staging sequence for dehumidication at each adjustment period is as follows:
Cool 1 ON at Humidity Setpoint + Humidity Deadband
Cool 2 ON at Humidity Setpoint + Humidity Deadband + 1% (LCS Dual Compressor Units)
Cool 2 OFF at Humidity Setpoint + 1% (LCS Dual Compressor Units)
Cool 1 OFF at Humidity Setpoint
8. The sequence for dehumidication with Energy Saver or Auxiliary Chilled Water Cooling is as follows:
Valve is OPENED to 100% at Humidity Setpoint + Humidity Deadband
Valve is CLOSED at Humidity Setpoint