56 • Mini dap4 User Manual
3) Settings in Mini-dap4 for gPod model
There are night time offsets to the temperature, humidity and CO
2
set points. There are also ad-
ditional settings for CO
2
high and Low level alarms.
a) gPod model
The Mini-dap4 is set to the gPod model at the factory and “gPOD” will appear on the main
screen of Mini-dap4. Please contact the Data Aire if your Mini-dap4 controller is not set to
the gPod model as required.
b) CO
2
control settings
To access the CO
2
level set point, press Menu button then enter the service level
password (default is 0000). After entering the password, use ↑/↓ button to advance to
Menu-B “Setpoint” then press enter and go to the CO
2
set point screen. Here you can
adjust the CO
2
level set point, dead band and CO
2
valve as desired.
CO
2
Set point
Set point: 1000ppm (100-5000ppm)
Dead band: 25ppm (25-1000ppm)
Min Valve On: 5s (0-32767s)
Valve PWM: 10% (0-100%)
Note: This CO
2
set point screen is not shown if the control is not set for CO
2
control in the
factory settings menu.
c) Temperature and humidity set point offsets for night time schedule.
To access the temperature and humidity set points, press Menu button then enter service
password (default is 0000). After entering the password, select Menu-C “Clock/Scheduler”
and go to the Night Schedule screen. Here you can adjust the offsets for temperature and
humidity during the night time schedule.
Night Schedule
Cooling offset: 5.0 (-30 to 10°F)
Heating offset: 5.0 (0 to 30 °F)
Humidify offset: 10% (0-30%)
Dehumidify offset: 10% (0-30%)
Note: Avoid selecting a cooling offset or heating offset that cause excessive power
consumption and/or lead to a system short cycle. (A warning message will appear under
such conditions). For instance, if cooling offset is set to minus 5°F and heating offset is
set to 1°F with 72°F Temp set point and 2°F dead band; during night schedule the
cooling set point is adjusted to 67° and heating set point is adjusted to 71°. This cause
the compressor to run at 69° (set point +dead band) and the heater to also run at 69°
(set point – dead band).