EasyManua.ls Logo

DayTronic 3000PLUS - Page 52

DayTronic 3000PLUS
88 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3KP64 - 3.28
3000PLUS WITH 5D64 INSTRUCTION MANUAL V. SB.2
SETUP STAGE 5: LIMITS
(
contd)
When the
3000PLUS
displays this . . . Do this . . .
5.e. Press
5.f. The instruments current
LIMITS LATCH MODE status will be displayed:
ON or OFF. In LATCHING mode (the ON state), when a high-limit or
low-limit violation is detected, that violation condition will remain in effect
regardless of the subsequent behavior of the auxiliary output reading
until limits are released (see Section 5.E for the different ways you can
accomplish this). When limits are NONLATCHING (the OFF state), any
detected limit violation condition will cease to occur as soon as the auxil-
iary output reading leaves the corresponding limit zone (or associated
hysteresis deadband).*
Press
to toggle between the two allowed states. When the desired latch mode
state is displayed, press
5.g. Press
5.h. The instruments current
LIMITS POLARITY status will be displayed: NOR-
MALLY CLOSED (NC) or NORMALLY OPEN (NO). This selection sets
the contact polarity of the 3000PLUS instruments limit output relays (for
LOGIC I/O connections, see Section 2.E).
Press
to toggle between the two allowed states. When the desired polarity state
is displayed, press
(contd)
ENTER
SCROLL
ENTER
ENTER
SCROLL
ENTER
ST
and
LM
are lit.
3. FRONT-PANEL CONFIGURATION
AND CALIBRATION
LIMITS POLARITY
SELECTIONS:
NC
NO
Daytronic Corporation
2211 Arbor Blvd. Dayton, OH 45439 (800) 668-4745
Tel: (937) 293-2566 Fax: (937) 293-2586 www.daytronic.com
LIMITS LATCH
MODE SELECTIONS:
ON
OFF
* Latching also applies to the
BETWEEN (OK) limit zone.
See Section 5.E for a complete
discussion of 3000PLUS limit
monitoring.

Related product manuals