EasyManua.ls Logo

DayTronic 3000PLUS - Page 54

DayTronic 3000PLUS
88 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3KP64 - 3.30
3000PLUS WITH 5D64 INSTRUCTION MANUAL V. SB.2
Daytronic Corporation
2211 Arbor Blvd. Dayton, OH 45439 (800) 668-4745
Tel: (937) 293-2566 Fax: (937) 293-2586 www.daytronic.com
SETUP STAGE 5: LIMITS
(contd)
When the
3000PLUS
displays this . . . Do this . . .
Use
and
as explained in Section 3.A to adjust the displayed number until the
desired low limit hysteresis value is obtained (expressed in measurement
units). Enter a value of zero (0, 0.0, etc.) to indicate no deadband.
NOTE: You will not be allowed to enter a negative number, or a number
that is greater than the
difference between the existing HIGH LIMIT and
LOW LIMIT values.
Then press
5.m. Press
5.n. The instruments currently effective
HIGH LIMIT setpoint value will be dis-
played (having the decimal-point precision specified in Step 2.f). See Step
5.h, above, for an explanation of limit zones.
Use
and
as explained in Section 3.A to adjust the displayed number until the
desired limit value is obtained (expressed in measurement units).
NOTE:
You should not enter a HIGH LIMIT that is less than the current LOW LIMIT.*
5.o. Press
5.p. The instruments currently effective
HIGH LIMIT HYSTERESIS value will
be displayed (having the decimal-point precision specified in Step 2.f).
This parameter lets you define a HYSTERESIS window (or deadband)
immediately below the GREATER THAN LIMIT ZONE defined by the cur-
rent HIGH LIMIT setpoint value (see Fig. 21, Section 5.E). The hysteresis
deadband is to prevent low-level signal noise from toggling the high-limit
relays on and off while the reading of Channel 2 remains in the neighbor-
hood of the setpoint.
(contd)
ENTER
ENTER
ENTER
ST
and
LM
are lit.
3. FRONT-PANEL CONFIGURATION
AND CALIBRATION
* Also, the absolute value of the
HIGH LIMIT value should not be
greater than that of the
FULL-
SCALE OUTPUT IN ENGINEER-
ING UNITS
entered in Step 2.i.

Related product manuals