24
5.2 ELECTRICAL CONNECTIONS FOR 230V MODELS
Execute the wiring following the directions of “Table 2” and diagrams on page 25.
WARNINGToensureanappropriatelevelofelectricalsafetyalwayskeepthe230Vpowersupplycablesapart(minimum4mm
intheopenor1mmthroughinsulation)fromlowvoltagecables(motorspowersupply,controls,electriclocks,aerialandauxiliary
circuitspowersupply),andfastenthelatterwithappropriateclampsneartheterminalboards.
WARNINGConnecttothepowersupply230V~±10%50Hzthroughamultipoleswitchoradifferentdevicethatcanensure
multipoledisconnectionfromthepowersupply,withacontactopeningof3mm.
WARNING Toconnecttheencodertothecontrolpanel,useonlyadedicatedcable3x0,22mm
2
.
Tabella 2 “collegamento alle morsettiere”
1-2 230V~±10%(50/60Hz)powersupplyinput
3-4-5
Operator1output230V~max600W
6-7-8
Operator2output230V~max600W(ifpresent)
9-10
230V~max150Woutputforopengatewarninglight(ifP052=0)orcourtesylight(ifP052>1)
11-12
Flashinglightoutput230V~max40W
13-14
13 (-)
“Boost”outputforelectric-lock,max1xart.110(ifP062=0),24Vpulseoutput,max5W(ifP062=1),
step by step (if P062=2), electro-brake output for not self-locking operators (if P062=3), output for
electric-lockpowersupplyviaexternalrelay(ifP062=4),outputforelectro-magnetspowersupplyfor
barriers(ifP062=5)ortemporizedoutput(ifP062>5).
14 (+)
15-16
Output24V max100mA;byselectingtheFL/WLjumper,youcanchoosethe230Flashoutputasa
24Voutput(ifthejumperissettoFL)orasaWarninglightoutput(ifjumpersettoWL).
Warning:theoutputcapacityallowstouseLEDflashinglightsonly
17-18
17 - N.C.
Input6FCC1.IfitintervenesitstopsM1closing.If unused, short circuit.
Iftheinstallationrequiresdifferentcomman-
dsand/oradditionaltothestandard,you
can configure each input to the required
rate.
Refer to Chapter
“Advanced Programming”.
18 - Com
19-20
19 - N.C.
Input5FCA1.IfitintervenesitstopsM1opening.If unused, short circuit.
20 - Com
21-22
21 - N.C.
Input4PHOTO1.Whenenabled(seeparameterP050 in the table), activation of
PHOTO1provokes:aninversionofdirection(duringclosing),thearrestofthemo-
vement(duringopening),preventthestart(gateclosed).If unused, short circuit.
22 - Com
23-24
23 - N.C.
Input3SAFETY.Ifactivated,itcausestheinversion.SeeP055andP056onthepara-
meterstable.If unused, short circuit.
24 - Com
25-26
25 - N.O.
Input2PED.Ifactivated,itopensmotornr.1only.
26 - Com
27-28
27 - N.O.
Input1START.Incaseofinterventionitprovokes:theoperatoropeningorclosing.It
mayoperateas“inversion”mode(P049=0)or“stepbystep”mode(P049=1).
28 - Com
29 Aerialsignalinput
30
Groundaerialinput
31-32
24V~powersupplyoutputforauxiliarydevices200mA
33-34
33 (+)
DE@NETmainsinput(unusedatthemoment)
34 (-)