5.1  ELECTRICAL CONNECTIONS FOR THE SPACE MODEL
! Risk of malfunction due to improper installation !
! Risk of personal injury and property damage due to electric shocks !
Execute the wiring following the directions of “Table 1” and diagram (Pag. 31).
WARNING To ensure an appropriate level of electrical safety  always keep the 230V power supply cables apart (minimum  4mm in the 
open or 1 mm through insulation) from low voltage cables (motors power supply, controls, electric locks, aerial  and auxiliary circuits 
power supply), and fasten the latter with appropriate clamps near the terminal boards.
WARNING Connect to the power supply 230 V ~± 10% 50 Hz through a multi pole switch or a different device that can ensure multi pole 
disconnection from the power supply, with a contact opening of 3 mm.
Table 1 “terminal board connections”
1-2-3-4 Motor 1 encoder output
5-6
Motor 1 output max 5A
7-8
7  (+)
Congurable 24V   output 1 max 5W (see P066 for values that can be selected)
8  (-)
9-13
9 - N.O.
Input 4. Unused
If  the  installation  requires  different 
commands and / or additional to the 
standard, you can  congure each in-
put to the required rate.
Refer to Chapter
 “Advanced Programming”.
13 - Com
10-13
10 - N.O.
Input 3. Unused
13 - Com
11-13
11 - N.O.
Input 2 START. In case of intervention it provokes: the operator opening or closing. It 
may operate as “inversion” mode (P049=0) or “step by step” mode (P049=1).
13 - Com
12-13
12 - N.C.
Input 1  PHOTO  1. When enabled (see parameter P050 in the table), activation of 
PHOTO 1 provokes: an inversion of direction (during closing), the arrest of the move-
ment (during opening), prevent the start (gate closed). If unused, short circuit.
13 - Com
14-15
14  (-)
Stabilized 24 V   power supply output for tested safety devices max 200mA
15  (+)
16-17
16  (+)
Congurable 24V   output 2 max 5W (see P062 for values that can be selected)
17  (-)
18 Aerial signal input
19
Ground aerial input
CON 1
Connection of motors metallic parts
CON 2
25 V ~ transformer power supply input
CON 3 Courtesy light output
CON 4 Input for NET-NODE / MEMONET connector
CON 5 Input for NET-EXP connector
J4 (jumper)
Operating mode selection jumper:
 (closed) = Normal functioning;
 (open) = Programming mode;