Protections
057-289 ISSUE: 1
Page 94 of 148
6.3 ELECTRICAL TRIP ALARMS
NOTE: The fault condition must be resolved before the alarm can be reset. If the fault
condition remains, it is not possible to reset the alarm (the exception to this is the Coolant
Temp High alarm and similar Active From Safety On alarms, as the coolant temperature could
be high with the engine at rest).
Electrical Trip Alarms are latching and stop the Generator but in a controlled manner. On initiation of
the electrical trip condition the module de-activates the Close Gen Output outputs to remove the load
from the generator. Once this has occurred the module starts the Cooling Timer and allows the engine
to cool off-load before shutting down the engine. To restart the generator the fault must be cleared
and the alarm reset.
Example:
1/2
Alarms
Gen Over Current
Electrical Trip
In the event of an alarm the LCD jumps to the alarms page and scrolls through all active alarms.
Electrical Trip Alarms are latching alarms and to remove the fault, press the Stop/Reset Mode
button on the module.
Fault
Description
2130 ID 1 to 4 Analogue Input
E to H High
NOTE: Due to module configuration the alarm message
that appears on the display may be different. For further details
of module configuration, refer to DSE Publication: 057-287
DSE6110 MKIII & DSE6120 MKIII Configuration Software
Manual.
The module detected that an analogue input value of a DSE2130
had risen above the Flexible Sensor High Alarm Trip level.
2130 ID 1 to 4 Analogue Input
E to H Low
NOTE: Due to module configuration the alarm message
that appears on the display may be different. For further details
of module configuration, refer to DSE Publication: 057-287
DSE6110 MKIII & DSE6120 MKIII Configuration Software
Manual.
The module detected that an analogue input value of a DSE2130
had fallen below the Flexible Sensor Low Alarm Trip level.
2130 ID1 to 4 Digital Input
A to H
NOTE: Due to module configuration the alarm message
that appears on the display may be different. For further details
of module configuration, refer to DSE Publication: 057-287
DSE6110 MKIII & DSE6120 MKIII Configuration Software
Manual.
The module detected that a digital input configured to create a fault
condition on a DSE2130 expansion module became active and the
appropriate LCD message displayed.
Continued over page…

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the DEEP SEA ELECTRONICS DSEGenset DSE6110 MKIII and is the answer not in the manual?

DEEP SEA ELECTRONICS DSEGenset DSE6110 MKIII Specifications

General IconGeneral
BrandDEEP SEA ELECTRONICS
ModelDSEGenset DSE6110 MKIII
CategoryControl Unit
LanguageEnglish

Related product manuals