21
Note: The fan step can be modified only if program mode is deactivated (see chapter 5.5).
Available settings: 1, 2, 3, 4 or A (automatic operation)
Factory setting: 1
Notes on setting: The fan step to be selected depends on the operating mode and the size of
the room. The table below is meant to assist you in finding the optimum fan
step.
Fan step max. room volume in m
3
for
purification
max. room volume in m
3
for humidification
Air changes per hour
1 2 3 4
1 155 77 52 39 155
2 195 97 65 49 195
3 280 140 93 70 280
4 340 170 113 85 340
A 155 77 52 39 155
In automatic operation the fan step is controlled automatically based on the
difference between the actual and the reference humidity value. Automatic
operation is active only if humidification is on. If humidification is inactive the
“A” setting corresponds to fan step “1”.
The following recirculation cycles per hour are recommended for air puri-
fication:
– Normal load: 1 – 2
– heavily polluted air (e.g. pollen, smoke, etc.): 3 – 4
5.4.2 Setting the fan step
Fan power
1
Fan power
New Value
Fan power
Old Value
Fan power
1
(see chapter 5.4.1)
(see chapter 5.4.3)
modify
confirm
cancel
1, 2, 3, 4 or A