4-20 mA values
It is strictly necessary to adjust the 4-20 mA values of the connected transducer. This is done like the
following example for a 4-20 mA mains transducer with the configuration of:
Power [kW]
Current out [mA]
Power import from grid
700 kW
20 mA
Power export to grid
-700 kW
4 mA
Press the dotted line in front of the value to modify it.
Testing procedure of the transducer signals
It is essential to test the transducer signals into the DEIF controller. Please follow these steps to verify the
good functionality. All 4-20 mA inputs may be used. In the example, the mains power transducer is used
(multi-configurable input 102).
Terminal
Designation
102
Not used
103
+ (4-20)
104
0 (com)