ASC commissioning guide 4189341077 UK
Nominal ratings
Menu
Function
Comments
6002
Adjust the rating of the installed
PV Panels.
For example 200 250 Wp modules are
installed. Adjust in this menu
200*250*10^-3=50 kW.
6005
Adjust the Q rating of the
inverter
If given. Otherwise, adjust to the same
value as 6006.
6006
Adjust the S rating of the
inverters.
For example three 20 kVA inverters are
installed. Adjust this menu to 3*20=60
kVA.
Emergency stop
The emergency stop will send a 0 kW reference to the PV plant and open the PV breaker if it is present.
The fail class can be selected to warning if the alarm input has to be used for other purpose.
Menu
Function
Comments
3490
Emergency stop details
Emergency stop alarm consists of sub
menus.
3491
Timer
If used as e-stop then select 0 sec.
3492
Relay output for PLC
OA
3493
Relay output for PLC
OB
3494
Enable this alarms
3495
Select fail class
If used as e-stop, then select S/D.