ASC commissioning guide 4189341077 UK
4. Measurements
The voltage and current measurements need to be connected and set up in the menus.
Function
Associated menus
PV IL1
S1
6003, I nominal
6043, CT primary
6044, CT, secondary
PV IL1
S2
PV IL2
S1
PV IL2
S2
PV IL3
S1
PV IL3
S2
Voltage measurements
Function
Associated menus
UL1
PV
6004, U nominal PV
6041, U PT primary
6042, U PT secondary
UL2
PV
UL3
PV
N
PV
If no PT is installed and the voltage is wired directly into the ASC, the ratio is set 1:1. For example 415:415 on
a 415 volt system.
Terminal
Function
Associated menus
85
UL1
BUS
6053, U nominal PV BUS
6051, U PT primary
6052, U PT secondary
86
87
UL2
BUS
88
N
BUS
89
UL3
BUS
Notice that the terminal for the neutral is placed between L2 and L3.