ASC commissioning guide 4189341077 UK
Mains Breaker is present
No control of the mains breaker is present. But it is necessary to wire in position feedbacks so the ASC
knows the status of the mains breaker. This is the case for none power management systems. (ASC is the
only DEIF controller in the system).
Feedback for the MB open
position
Feedback for the MB closed
position
Power management CAN bus
Power management
communication
7841, CANport select
7870, actions at CAN failure
Power management
communication
Notice that the CAN bus line has to be terminated in each end with a 120 Ohm resistor.
Stand-alone system
The mentioned parameters, wiring and settings must be configured when it is not a power management
system.
Genset #1 breaker is closed
Genset #2 breaker is closed
Genset #3 breaker is closed
Genset #4 breaker is closed
Genset #5 breaker is closed
Genset #6 breaker is closed
Maximum 16 gensets can be configured