ASC commissioning guide 4189341077 UK
Synchronise and close the MB when there is generation in the plant. Current will flow out of the plant
(depending on load demand):
Power [kW]
Current out [mA]
MB closed position
-349 kW
8 mA
Display view, translated (suggestion)
Display view master language
PV380.0 380.0 380.0V
Mains kW -349kW
PROTECTION SETUP
PROT CTRL I/O SYST
PV380.0 380.0 380.0V
Analog 102 -349mA
PROTECTION SETUP
PROT CTRL I/O SYST