Installation and Setup Installing Array Hardware
2–13
PS5500 Environmental Requirements
You must meet these environmental requirements:
Only operate an enclosure from a power source with a voltage range of 100 to
240 VAC.
Make sure your power source has sufficient electrical overload protection.
In North America, connect the enclosure to a source of power with over-
current protection provided by a double pole 20A or less (LISTED circuit
breaker to UL489). In Europe, the over-current protection must be provided
by 20A or less (IEC circuit breakers).
Have sufficient space for air flow in front of and behind the array and ensure
that the location is properly vented.
Follow the PS5500 technical specifications. See Table 2-6.
Table 2-6: PS5500 Technical Specifications
Component Requirement
Weight without disk drives 77 pounds (35kg)
Weight with disk drives 177 pounds (80kg)
Operating temperature 41 to 95 degrees F (5 to 35degrees C)
Storage temperature 34 to 140 degrees F (1 to 60 degrees C)
Operating altitude 0 to 10,000 feet (0 to 3048 meters)
Operational relative humidity 20% to 80% non-condensing
Storage relative humidity 5% to 80% non-condensing
Thermal output (fully-loaded array) 3400 BTU/hour
Operational shock 5g peak 1/2 sin, for 10ms
Operational vibration .21grms 5 to 500 Hz Random
Input voltage 100 to 240 VAC (auto-sensing)
Input frequency 50 - 60Hz
System input power 1400 VA (maximum)
Each power supply 440 watts DC output
Maximum input power: 0.7 KVA
Input current: 7 – 3.5A
Height/Width/Depth 6.89” x 19.01” x 31.9” (17.5cm x 48.3cm x 81.0cm)