122
Model RT-10K3P RT-15K3P RT-20K3P
Physical
Dimensions
(W × D × H)
440 ×
649 ×
88.2 mm
(17.3” × 25.6”
× 3.5”)
440 × 760 × 88.2 mm
(17.3” × 29.9” × 3.5”)
Weight
16.6 kg (36.6 lb) 22 kg (48.5 lb) 22.5 kg (49.6 lb)
Environment
Operating Altitude
0 m ~ 3000 m (0 ft ~ 9900 ft);
0 m ~ 1000 m (0 ft ~ 3300 ft) without derating
Operating
Temperature
*2
0°C ~ 55°C (32°F ~ 131°F)
Storage
Temperature
-15°C ~ 55°C (5°F ~ 131°F)
Relative Humidity
5% ~ 95% (non-condensing)
NOTE:
1.
*
1
The rated output power of the UPS needs to be de-rated to 70%.
2.
*
2
When the operating temperature is at 40°C ~ 55°C (104°F ~ 131°F), the rated output
power of the UPS needs to be de-rated to 75%. When connected to the Delta lithium-ion
battery pack (optional), the UPS operating temperature is 0°C ~ 45°C (32°F ~ 113°F).
3. Please refer to the rating label for the safety certification.
4. All specifications are subject to change without prior notice.
5. When the UPS is connected to the optional Delta Power Distribution Box (PDB), the
operating temperature is 0°C~ 40°C (32°F ~ 104°F).
6. Because the optional dust filter will affect the air volume, the rated output power of the
UPS needs to be de-rated to 80% at 0°C~ 40°C (32°F ~ 104°F).
7. Because the optional dust filter will affect the air volume, the rated output power of the
UPS needs to be de-rated to 60% at 40°C ~ 55°C (104°F ~ 131°F).