www.deltapowersolutions.com
Delta UPS - Amplon Family
User Manual
The power behind competitiveness
RT Series, Single Phase
5/ 6/ 8/ 10 kVA
ESC
BATTERY PACK

Other manuals for Delta Amplon Series

Questions and Answers

  • M
    mnguyenAug 20, 2025
    What to do if my Delta Amplon shows 'Output Overload Shutdown'?
    • B
      Brenda MartinezAug 20, 2025
      If your Delta UPS is showing an 'Output Overload Shutdown' message, it means the UPS is overloaded. Check the power consumption of the connected devices and remove any unnecessary loads.
  • L
    leslieharrisAug 22, 2025
    Why does my Delta Amplon UPS show 'INV IGBT Over Heat Shutdown'?
    • M
      Mary FordAug 22, 2025
      The 'INV IGBT Over Heat Shutdown' error on your Delta UPS indicates that the vents may be blocked or the UPS has an internal fault. Check if the vents are blocked. If not, contact service personnel.
  • M
    Mr. Joel HughesAug 25, 2025
    Why is my Delta UPS showing 'PFC Over Heat Shutdown'?
    • D
      David DavidAug 25, 2025
      If your Delta UPS displays a 'PFC Over Heat Shutdown' message, it could be due to blocked vents or an internal fault. Check the vents to ensure they are not blocked. If the problem persists, contact service personnel.
  • V
    Valerie MunozAug 27, 2025
    What to do if my Delta UPS says 'Battery Disconnected'?
    • K
      keithwilliamsAug 27, 2025
      If your Delta UPS shows 'Battery Disconnected', verify that the UPS is correctly connected to the external battery pack(s). If the connections are secure, it's possible the battery/batteries are damaged, and you should contact service personnel.
  • S
    Samantha GallagherAug 28, 2025
    What to do if my Delta Amplon displays 'DC Bus Over Shutdown'?
    • W
      Willie MurphyAug 28, 2025
      If your Delta UPS is showing a 'DC Bus Over Shutdown' message, it could be due to capacitive or inductive loads on the output, or an internal fault. First, remove any capacitive or inductive loads. If the issue continues, contact service personnel.
  • L
    Lisa SmithAug 30, 2025
    Why does my Delta UPS have 'Input Fuse Open'?
    • D
      Dawn CastilloAug 30, 2025
      The 'Input Fuse Open' error on your Delta UPS means that the input fuse is melted or the input relay is open. Contact service personnel to resolve this issue.
  • E
    Eric JonesAug 31, 2025
    What does 'Charger Fault' mean on my Delta Amplon?
    • R
      Raymond ClarkAug 31, 2025
      The 'Charger Fault' message on your Delta UPS indicates an internal fault. Contact service personnel for assistance.
  • E
    eugene98Sep 2, 2025
    What does 'INV Volt Abnormal' mean on my Delta Amplon?
    • E
      Elizabeth JonesSep 2, 2025
      The message 'INV Volt Abnormal' on your Delta UPS indicates an internal fault. Contact service personnel.
  • T
    Thomas SheltonSep 4, 2025
    What does 'PFC Soft Start Fail' mean on my Delta UPS?
    • M
      Melissa BurgessSep 4, 2025
      The 'PFC Soft Start Fail' message on your Delta UPS indicates an internal fault. Contact service personnel.
  • E
    Edward MartinezSep 6, 2025
    What does 'DC Bus Under Shutdown' mean on my Delta Amplon UPS?
    • T
      Tamara KleinSep 6, 2025
      The 'DC Bus Under Shutdown' message on your Delta UPS indicates an internal fault. Contact service personnel.

Summary

Important Safety Instructions

1.1 Safety Instructions

General safety guidelines for installation, connection, and usage of the UPS.

1.2 Standard Compliance

Lists the safety and compliance standards the product adheres to.

1.3 Storage

Guidelines for storing the UPS before installation and after usage.

Introduction

2.1 General Overview

Overview of the Delta UPS RT Series, highlighting its capabilities and ratings.

2.2 Exterior & Dimensions

Details the physical dimensions and external configuration of the UPS unit and its components.

2.3 Package List

Lists all included accessories and components for the UPS package.

Operation Panel

3.1 LED Indicators

Explains the function and meaning of the UPS's LED indicators.

3.2 Multi-function Buttons

Describes the functions and operations of the UPS's multi-function buttons.

3.3 LCD Display

Details the LCD display interface, icons, and mode diagrams.

Rear Panel

MINI Slot

Describes the slot for communication expansion cards like SNMP or MODBUS.

Dry Contacts

Explains input and output dry contacts for control signals and event notifications.

REPO Port

Details the REPO port for emergency shutdown and remote control.

RS-485 Port

Covers connection to a computer for monitoring UPS status via RS-485.

RS-232 Port

Explains the RS-232 port for communication, configuration, and firmware upgrades.

USB Port

Describes the USB port for computer connection, monitoring, and configuration.

Output Breaker(s)

Explains the function of output breakers to prevent overload damage.

Output Sockets

Details the sockets for connecting loads to the UPS output.

Manual Bypass Switch

Describes the switch for manual bypass mode during maintenance.

External Battery Connector

Details the connector for external battery packs and provides specifications.

Communication Interfaces

5.1 RS-232 Port

Explains the RS-232 port's functions, pin assignment, and hardware specifications.

5.2 REPO Port

Describes the REPO port's function for emergency shutdown and configuration.

5.3 MINI Slot

Details the MINI slot for installing communication cards like SNMP or MODBUS.

5.4 USB Port

Explains the USB port's functions for computer connection, configuration, and firmware upgrade.

5.5 Dry Contacts

Covers input and output dry contacts for control signals and event notifications.

5.6 External Battery Connector

Details the connector for external battery packs and provides specifications.

Installation

6.1 Rack Mounting

Provides instructions for mounting the UPS in a standard rack using rail kits.

6.2 Tower Mounting

Details the procedure for installing the UPS in an upright tower position using included stands.

6.3 PDB Disassembly & Installation

Outlines precautions, disassembly, and assembly procedures for the PDB.

6.4 Battery; Battery Pack Replacement

Explains the step-by-step process for replacing the UPS batteries or battery packs.

Connection and Wiring

7.1 UPS Connection Warnings

Highlights important warnings and recommendations for connecting the UPS to mains and loads.

7.2 Input;Output Connection

Covers cable selection, connection diagrams, and backfeed protection.

Operation

8.1 Start-up

Details the procedures for starting up the UPS with AC input or in cold-start battery mode.

8.2 Turn-off

Explains the correct procedure for shutting down the UPS and its connected loads.

8.3 Operation Mode

Describes the different operating modes of the UPS, such as Online, ECO, and Bypass.

LCD Display & Settings

9.1 Initial Setting Screen

Guides users through the initial setup of language, voltage, and other parameters upon first power-on.

9.2 Main Menu

Explains how to navigate and access the Measurement, Setting, Control, and Maintenance menus.

Maintenance

12.1 UPS

Covers UPS cleaning and regular inspection procedures.

12.2 Batteries

Provides guidance on battery care, lifespan, and replacement.

12.3 Fans

Advises on checking fan operation and seeking service for replacement.

Delta Amplon Series Specifications

General IconGeneral
CategoryUPS
TopologyDouble Conversion
Transfer Time0 ms
Battery TypeSealed Lead-Acid (SLA)
DimensionsVaries by model
WeightVaries by model
ModelAmplon Series
TypeOnline
Input Voltage208/230/240VAC
Output Voltage208/230/240VAC
Output Voltage Regulation+/- 1%
Frequency Range50/60 Hz
EfficiencyUp to 96%
Communication InterfaceRS-232, USB, SNMP
Operating Temperature0°C to 40°C
Storage Temperature-15°C to 45°C
Relative Humidity0-95% non-condensing
CoolingFan cooling
Form FactorTower/Rackmount
CertificationsCE