Delta UPS - Amplon Family
User Manual
The power behind competitiveness
MX Series, Single Phase
1.1/ 2/ 3 kVA

Questions and Answers

  • P
    Patricia MayAug 9, 2025
    What to do if Delta UPS is overloading?
    • J
      josegarciaAug 9, 2025
      If the Delta UPS is overloading, as indicated by the icon and warning code flashing on the LCD display with an alarm sounding every second, the suggested solution is to remove excess loads from the UPS output.
  • D
    daniel48Aug 14, 2025
    What to do if Delta UPS shows fault code 43?
    • E
      Erin HodgesAug 14, 2025
      If your Delta UPS displays fault code 43 and the icon is lit on the LCD display with a continuous alarm, it means the UPS shut down automatically due to an overload at the output. Remove some of the connected devices to decrease the load and then restart the UPS.
  • G
    Gwendolyn GonzalezAug 19, 2025
    What to do if Delta UPS shows fault code 14?
    • G
      gabriellemurilloAug 19, 2025
      If fault code 14 is shown on the Delta UPS and the alarm is continuously sounding, it indicates that the UPS shut down automatically because a short circuit occurred at the output. You should check the output wiring and any connected devices for a short circuit.
  • W
    Wesley ScottAug 25, 2025
    Why is my Delta UPS battery backup time shorter than expected?
    • J
      josephashleyAug 25, 2025
      There are a couple of reasons why your Delta UPS battery backup time might be shorter than the nominal value: * The batteries may not be fully charged. In this case, charge the batteries for at least 5 hours and then check the capacity. * The batteries might be defective.
  • J
    James BauerAug 29, 2025
    What to do if the icon and warning code flashing on Delta UPS LCD display?
    • B
      Brittany CunninghamAug 29, 2025
      If the icon and warning code are flashing on the LCD display and the alarm is sounding every 2 seconds, it could be due to a few reasons: * REPO function is activated. To solve this, set the circuit in a closed position to disable the REPO function. * Line and neutral conductors of UPS input are reversed. Rotate the mains power socket by 180° and then connect to the UPS system. * The external or internal battery is incorrectly connected. Check if all batteries are well connected.
  • G
    Garrett WrightSep 3, 2025
    What to do if Delta UPS has no indication and alarm?
    • D
      David FoxSep 3, 2025
      If your Delta UPS has no indication and alarm, even when the mains is normal, consider these possibilities: * The AC input power is not connected well. Check if the input power cord is firmly connected to the mains. * The AC input is connected to the UPS output. Plug the AC input power cord to the AC input correctly.

Delta Amplon MX Series Specifications

General IconGeneral
TopologyDouble Conversion Online
DisplayLCD
TypeOnline UPS
Output Voltage208/220/230/240 Vac (single phase)
Output Frequency50/60Hz
Communication PortsRS-232, USB, SNMP (optional)
Protection FeaturesOverload, Short Circuit, Over Temperature
Operating Temperature0-40°C
Humidity0% to 95% (non-condensing)
DimensionsVaries by model
WeightVaries by model