Chapter 8 Operation
41
In Progress...
Self Diagnosis
Press and hold the button
for 3 seconds and release it
after you hear one beep.
100
75
%
%
BATTERY
1
168
min
Runtime
Input
Output
0.0V
230.0V
0.0Hz
50.0Hz
4
Once the UPS runs normally, switch on the output protective device (see
Figure 7-1) installed between the UPS and the loads.
NOTE :
To prevent the UPS from activating the overload protection mechanism
during start-up process, please turn on the high-power loads first and
then low-power loads.
8.2 Turn-o
1
Make sure all of the loads connected to the UPS are o.
2
(1) Press and hold the ON/ OFF button (
) for 3 seconds, (2) release it after
you hear one beep, (3) use the Scrolling UP or Down button (
/
) to
select
'Yes'
, and (4) press the Enter button (
) to conrm your selection.
3
Switch o the input protective device (see Figure 7-1) and output protective
device (see Figure 7-1).
4
After the LCD backlight goes dim and the fans stop completely, switch o the
battery breaker to ensure that there is no remaining battery power.