Delta UPS - Modulon Family
The power behind competitiveness
www.deltapowersolutions.com
DPH Series, Three Phase
200-500 kVA
User Manual

Table of Contents

Questions and Answers

  • J
    jillgrantSep 12, 2025
    What does 'Mains Input Volt Phase Seq Abnormal' mean on my Delta Modulon DPH UPS?
    • T
      Timothy CookSep 12, 2025
      If your Delta UPS shows 'Mains Input Volt Phase Seq Abnormal', it means the wiring is incorrect. Check the wiring and phase sequence of the main AC source, and contact service personnel for assistance.
  • R
    Robert ColeAug 25, 2025
    What to do if my Delta Modulon DPH shows 'Battery Disconnected'?
    • R
      ronaldcherryAug 25, 2025
      If your Delta UPS displays a 'Battery Disconnected' message, first check if the batteries are properly connected. Also, verify if the battery breaker is turned off; if so, turn it on. If the alarm persists after these steps, contact service personnel for assistance.
  • B
    Brian WheelerAug 25, 2025
    How to fix Delta Modulon DPH UPS when 'Mains Input Volt/ Freq Out Range'?
    • C
      Christopher RoseAug 26, 2025
      If your Delta UPS shows a 'Mains Input Volt/ Freq Out Range' error, first check if the input breaker or switch is turned off and turn it on if it is. Then, check if the main AC source's voltage or frequency is abnormal and wait for it to be restored. If the alarm persists, contact service personnel.
  • N
    Nancy NorrisSep 23, 2025
    What does 'Charger Over Heat Shutdown' mean on my Delta UPS?
    • S
      Sandra MillerSep 23, 2025
      If your Delta UPS displays 'Charger Over Heat Shutdown', check if any foreign matter blocks the fans and remove it. If the problem persists, contact service personnel.
  • M
    Mrs. Cathy MooreSep 13, 2025
    What should I do if my Delta Modulon DPH UPS reports 'Battery Reversed'?
    • D
      Devin MurphySep 13, 2025
      If your Delta UPS reports 'Battery Reversed', check the battery wiring. If there is any error or abnormality, contact service personnel.
  • J
    Joan RiveraSep 18, 2025
    What does 'EXTCAN Bus Abnormal - Physical' mean on my Delta UPS?
    • D
      Diane ConleySep 22, 2025
      If your Delta UPS displays 'EXTCAN Bus Abnormal - Physical', check if the parallel cable is firmly connected and contact service personnel.
  • C
    Chris MunozSep 6, 2025
    What does it mean if my Delta Modulon DPH displays 'Battery End of Discharge Imminent'?
    • J
      Joshua MaySep 6, 2025
      If your Delta UPS displays 'Battery End of Discharge Imminent', and there is no bypass power feeding the system, shut down the connected loads in accordance with normal procedures as soon as possible, because the battery voltage is lower than the alarm value.
  • P
    Paul MurraySep 7, 2025
    What does it mean if my Delta UPS displays 'Battery End Of Discharge'?
    • B
      Barry PhillipsSep 7, 2025
      If your Delta UPS displays 'Battery End Of Discharge', and there is no bypass power feeding the system, shut down the connected loads in accordance with normal procedures as soon as possible, because the battery voltage is lower than the End-of-Discharge setup value.
  • A
    Andrew ShawSep 23, 2025
    What does 'INV #n PLL Bus Abnormal' mean on my Delta Modulon DPH UPS?
    • J
      Jerry HayesSep 23, 2025
      If your Delta UPS displays 'INV #n PLL Bus Abnormal', confirm if the main AC source’s voltage is abnormal. If it is, wait for the main AC source to be restored to normal. If not, contact service personnel.
  • C
    Corey DavisAug 30, 2025
    Why Delta UPS shows 'Bypass Input Volt Out Range'?
    • J
      Jonathon MoraAug 30, 2025
      If your Delta UPS shows a 'Bypass Input Volt Out Range' error, it could be due to the bypass breaker or switch being turned off, or the bypass AC source's voltage being abnormal. Check if the bypass breaker or switch is off and turn it on if it is. Also, check if the bypass AC source's voltage is abnormal and wait for it to be restored. If the alarm persists, contact service personnel.

Delta Modulon DPH series Specifications

General IconGeneral
ModelDelta Modulon DPH series
CategoryUPS
Frequency50/60 Hz
TopologyDouble Conversion Online
Input Voltage380/400/415 V (3-phase, 3-wire + PE or 3-phase, 4-wire + PE)
Output Voltage380/400/415 V (3-phase, 3-wire + PE or 3-phase, 4-wire + PE)
Communication InterfaceRS232, SNMP, Modbus
Operating Temperature0°C to 40°C
Relative Humidity0 to 95% (non-condensing)
DimensionsVaries by model
WeightVaries by model