Delta Modulon DPH series - User Manual

Delta Modulon DPH series
232 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
Delta UPS - Modulon Family
The power behind competitiveness
www.deltapowersolutions.com
DPH Series, Three Phase
200-500 kVA
User Manual

Table of Contents

Questions and Answers

  • R
    Robert ColeAug 25, 2025
    What to do if my Delta Modulon DPH shows 'Battery Disconnected'?
    • R
      ronaldcherryAug 25, 2025
      If your Delta UPS displays a 'Battery Disconnected' message, first check if the batteries are properly connected. Also, verify if the battery breaker is turned off; if so, turn it on. If the alarm persists after these steps, contact service personnel for assistance.
  • B
    Brian WheelerAug 25, 2025
    How to fix Delta Modulon DPH UPS when 'Mains Input Volt/ Freq Out Range'?
    • C
      Christopher RoseAug 26, 2025
      If your Delta UPS shows a 'Mains Input Volt/ Freq Out Range' error, first check if the input breaker or switch is turned off and turn it on if it is. Then, check if the main AC source's voltage or frequency is abnormal and wait for it to be restored. If the alarm persists, contact service personnel.
  • P
    palmerkeithAug 26, 2025
    What to do if Delta UPS indicates 'Output Breaker Off'?
    • S
      Sandra RodriguezAug 26, 2025
      If your Delta UPS is indicating 'Output Breaker Off', check if the output breaker or switch is turned off. If it is, turn it on. If the alarm message continues after this, contact service personnel for further assistance.
  • P
    Patricia BrownAug 27, 2025
    What to do if Delta Modulon DPH displays 'Bypass Breaker Off'?
    • S
      Savannah TorresAug 27, 2025
      If your Delta UPS displays 'Bypass Breaker Off', and you have a single input application, check if the input breaker or switch is turned off and turn it on. If you have a dual input application, check if the bypass breaker or switch is turned off and turn it on. If the alarm message persists, contact service personnel.
  • R
    Rodney NelsonAug 27, 2025
    What to do if Delta Modulon DPH displays 'Battery Breaker OFF'?
    • A
      Anne ZimmermanAug 27, 2025
      If your Delta UPS displays a 'Battery Breaker OFF' message, check if the external battery breaker is turned off and turn it on if it is. If the alarm message persists, contact service personnel.
  • M
    Michelle MarshallAug 28, 2025
    What to do if Delta Modulon DPH displays 'Emergency Pwr Of'?
    • T
      Travis PaceAug 28, 2025
      If the Delta UPS displays 'Emergency Pwr Of', check if the EPO button is pressed. If it is, restart the UPS using the normal start-up procedures after resolving any abnormalities. If the alarm persists, contact service personnel.
  • S
    Sara WilliamsAug 29, 2025
    What to do if my Delta Modulon DPH displays 'Output Overload Shutdown'?
    • G
      Gloria ConleyAug 29, 2025
      If your Delta UPS displays 'Output Overload Shutdown', it means the connected loads have exceeded the rated value for a prolonged period. After overload shutdown, the loads will be supplied by the bypass. Decrease the loads to allow the system to restart automatically. If the alarm persists, contact service personnel.
  • E
    Eric WilsonAug 30, 2025
    What to do if Delta Modulon DPH UPS displays 'Battery Over Temperature'?
    • J
      julie62Aug 30, 2025
      If your Delta UPS displays 'Battery Over Temperature', improve ventilation to reduce the battery temperature. Also, check if the batteries are abnormal; if so, contact service personnel.
  • C
    Corey DavisAug 30, 2025
    Why Delta UPS shows 'Bypass Input Volt Out Range'?
    • J
      Jonathon MoraAug 30, 2025
      If your Delta UPS shows a 'Bypass Input Volt Out Range' error, it could be due to the bypass breaker or switch being turned off, or the bypass AC source's voltage being abnormal. Check if the bypass breaker or switch is off and turn it on if it is. Also, check if the bypass AC source's voltage is abnormal and wait for it to be restored. If the alarm persists, contact service personnel.
  • F
    Frank WhiteAug 23, 2025
    What to do if my Delta Modulon DPH displays 'Output Overload Warning'?
    • P
      paul17Aug 25, 2025
      If your Delta UPS is showing an 'Output Overload Warning', it means the connected loads are exceeding the rated value. You should decrease the loads connected to the UPS.

Delta Modulon DPH series Specifications

General IconGeneral
ModelDelta Modulon DPH series
CategoryUPS
Frequency50/60 Hz
TopologyDouble Conversion Online
Input Voltage380/400/415 V (3-phase, 3-wire + PE or 3-phase, 4-wire + PE)
Output Voltage380/400/415 V (3-phase, 3-wire + PE or 3-phase, 4-wire + PE)
Communication InterfaceRS232, SNMP, Modbus
Operating Temperature0°C to 40°C
Relative Humidity0 to 95% (non-condensing)
DimensionsVaries by model
WeightVaries by model