6-36
Modulon DPH Series
6.3.2 Battery Mode Turn-off Procedures
WARNING:
1. For parallel units, ensure that every operation procedure mentioned below is
synchronized to all parallel UPSs.
2. For parallel application, if you just want to operate a specific UPS but not all
parallel ones, please contact service personnel.
1
In battery mode, the LCD shows the following screen (Figure 6-48) and the tri-color
LED indicator illuminates yellow. For the tri-color LED indicator location, please refer to
Figure 2-11.
Battery
POWER FLOW
Maintenance
Bypass
Bypass
Mains
90 %
5 mins
Load
30 %
MEASUREMENT
Power Flow
UPS-1.1 SETUP MAINTENANCE
Power Flow
Summary
System Status
LOG IN
User
2
WARNING
10:15
May 25,2018
ON/ OFF
Button
(Figure 6-48: Battery Mode Screen & ON/ OFF Button Location)
2
Press the ON/ OFF button ( ) once and the following screen will pop up to ask you
if you want to power off the UPS’s inverter. Please select ‘YES’.
MEASUREMENT
Power Flow
UPS-1.1 SETUP MAINTENANCE
No
Yes
LOG IN
User
POWER OFF ?
Transfer to Bypass without Protection!
2
WARNING
Battery
10:15
May 25,2018
(Figure 6-49: Power Off Reminder Screen)